NTEP
CERTIFICATION #92-152 |
The
INFW scale meter is a microprocessor-based indicator/
controller with enhanced features that allow you to easily configure
the unit for virtually any application. It is compatible with
most strain gage sensors such as load cells and pressure transducers.
Shown
with LC101 Series
Load Cell Sold Seperately
|
INFW
Selectable Scale Divisions, Selectable Classes I (III, IIIL, or
IV) and Handbook 44 Certification
6 Digits
2 or 5 Coordinate
Linearization of Input Signals
Four Isolated
Open Collector Outputs
Wide Selection
of dc Voltage and Current Ranges
Ratiometric
Inputs
Tare-Fixed,
Auto or Sequential
1.5 to 11
and 24 Vdc Sensor Excitation
Large Digital
Offset Capabilities Enabling Easy Scaling in Engineering Units
Smart Filtering
Detects the Difference Between a Spike or Process Change (Patent
Applied For)
Selectable
Decimal Point and Read Rates of up to 13 Readings/Sec
Peak and Valley
Detection and Memory
Configurable
Via Front Pushbuttons or Via RS-232 or RS-485
OPTIONS
Isolated Dual 7 Amp Form C (SPDT) Relays
Isolated Parallel
BCD Output
Isolated Analog
Output of 0-10 Vdc, 0-5 Vdc, 1-5 Vdc, 0-20 mA dc and 4-20 mA dc
Isolated Serial
RS-232
Isolated RS-485,
Addressable up to 199 Units
The INFINITY®
scale meter can be configured, via the five front-panel pushbuttons
and/or the optional serial communications boards, to accept any
of a variety of dc voltage ranges (some ranges plus unipolar or
bipolar are first selected via a jumper located at the top of
the instrument housing) and display them in engineering units.
Standard features include normal or sequential tare, peak or valley
recall, tare limit, and a high resolution A/D converter with digital
scaling and offset. Other features include dual relay or BCD output,
isolated analog output, RS-232 or RS-484 serial communications
options, auto or sequential tare, class selection, and display
of units of measure. Self-diagnostics are performed automatically
on power-up.
These meters provide both software and hardware lockout configurations
which let you define the parameters, from setpoint adjustment
to total reprogramming. Users can scale and offset their input
signal into any engineering units desired. This is accomplished
by the use of an exclusive two or five data point method of scale
and offset for linearization of input signals transmitted from
a sensor. The meter provides a choice of sensor excitations of
1.5 to 11 Vdc or 24 Vdc for sensors such as load cells, strain
gages, and pressure transducers.
|
INFZW
Split Meter
|
Self-Adjusting
Weight Assemblies
TWA5 Load Cell
Included
Available from
OMEGADYNE,
INC. |
SPECIFICATIONS
Accuracy:
▒0.005% rdg
Span Temperature Coefficient: ▒15 ppm/░C
Step Response: 1 sec to 99.9%
Warmup to Rated Accuracy: 55 min
Operating Ambient: 0 to 50░C (32 to 122░F), 95%RH, non-condensing
Storage Ambient: -40 to 85░C (-40 to 185░F)
Power: 115 or 230 Vac, 49-400 Hz; 10 to 32 Vdc
Power Consumption: 6 W nominal, 10 W max.
Normal Mode Rejection: 60 dB
Common Mode Rejection: 120 dB
Common Mode Voltage: 1500 V peak per Hv test
Conversion: dual-slope technique
Reading Rate: 3/sec or 13/sec, 60 Hz; 3/sec or 12/sec,
50 Hz
Display: red or green 6-digit, 14-segment, 13.7 mm (0.54");
4 alarm indicators
Dimensions: 48 H x 96 W x 165 D mm (1.89" x 3.78" x 6.5")
Panel Cutout: 45 H x 92 W mm (1.772" x 3.622"); 1/8 DIN
Weight: 574 g (1.27 lb)
TTL Outputs: four, isolated open collector; rated 150 mA
at 1 V sink, 30 V open
BCD Output: isolated, tri-state, TTL/CMOS compatible;
external 5 V supply for isolated; internal 5 V supply for non-isolated
Dual Relays: form C, 7 A at 30 Vdc or 230 Vac
Four Relay Option: dual 7A relays and dual 1 A relays
Analog Output: 0-5 V/1-5 V/0-10 V/0-20 mA/4-20 mA, user
selectable; 354 Vp isolation; 15-bit resolution; 0.1% accuracy,
50 msec step response
RS-232 Communications: 300/600/1200/2400/4800/9600/19.2k
baud; RJ11 4-wire connection; complete program setup and message
display capability; programmable to transmit current display,
alarm status, min/max, actual measured input value and status
RS-485 Communications: 300/600/1200/2400/4800/9600/19.2k
baud; RJ12 6-wire connection; addressable from 0 to 199
Voltage Input Ranges: 0-100 mV, 0-1 V, 0-5 V, 1-5 V, 0-10
V, 0-100 V, ▒50 mV, ▒500 mV, ▒5 V, ▒50 V
Current Input Ranges: 0-20 mA, 4-20 mA
Input Configuration: single-ended
Polarity: unipolar/bipolar, programmable
Span Adjustment: +0.00001 to 500,000, programmable
Offset Adjustment: 0 to 999,999 or 0 to -99,999; programmable
Sensor Excitation: 10 V at 30 mA for bridge; 24 V at 25
mA for loop power
To
Order (*insert
number code to complete model #) Prices Shown in U.S. Dollars
Basic
Model
|
Power/
Display
|
Control
Output
|
Analog
Output
|
Serial
Output
|
Input
Signal
|
Description
|
Price
|
INFW
|
(
* )
|
(
* )
|
(
* )
|
(
* )
|
(
* )
|
Strain
gage/load cell panel meter |
$545
|
|
(
* )
|
(
* )
|
(
* )
|
(
* )
|
(
* )
|
Strain
meter with remote display |
$595
|
|
0
|
|
|
|
|
115
Vac power, red LED display |
N/C
|
|
1
|
|
|
|
|
230
Vac power, red LED display |
N/C
|
|
2
|
|
|
|
|
115
Vac power, green LED display |
N/C
|
|
3
|
|
|
|
|
230
Vac power, green LED display |
N/C
|
|
|
0
|
|
|
|
Four
NPN open collector transistors |
N/C
|
|
|
1
|
|
|
|
Isolated
parallel BCD |
$110
|
|
|
2
|
|
|
|
Two
7 A relays |
$75
|
|
|
3
|
|
|
|
Two
7 A relays and two 1 A relays |
$175
|
|
|
|
0
|
|
|
No
analog output |
N/C
|
|
|
|
1
|
|
|
Isolated
analog output |
$110
|
|
|
|
|
0
|
|
No
serial output |
N/C
|
|
|
|
|
1
|
|
Isolated
RS-232 |
$110
|
|
|
|
|
2
|
|
Isolated
RS-485 |
$110
|
|
|
|
|
|
(
* )
|
Specify
range signal from chart below.* |
N/C
|
INPUT
SIGNAL
Range
Code
|
Range
|
|
Range
Code
|
Range
|
|
Range
Code
|
Range
|
DC1
|
0-100
mV
|
|
DC5
|
0-10
Vdc
|
|
DC9
|
▒5
Vdc
|
DC2
|
0-1
Vdc
|
|
DC6
|
0-100
Vdc
|
|
DC10
|
▒50
Vdc
|
DC3
|
0-5
Vdc
|
|
DC7
|
▒50
mVdc
|
|
C1
|
0-20
mA
|
DC4
|
1-5
Vdc
|
|
DC8
|
▒500
mVdc
|
|
C2
|
4-20
mA
|
OPTIONS
Model
|
Description
|
Price
|
|
Model
|
Description
|
Price
|
BL
|
Blank
Lens |
$15
|
|
9SC4
|
9-pin
RS-485 connector |
$30
|
FS
|
Special
Calibration |
$25
|
|
25SC2
|
25-pin
RS-232 connector |
$30
|
9SC2
|
9-pin
RS-232 connector |
$30
|
|
25SC4
|
25-pin
RS-485 connector |
$30
|
Ordering
Examples:
1.)
INFW-0200-DC7,
Standard Panel
Meter with
two relays,
▒50 mV input,
115 Vac power
and red LED
display, $595
+ 75 = $670.
2.)
INFZW-2210-DC1
Split Meter,
two relays,
analog output
and 0-100 mVdc
input, 115
Vac power and
green LED display,
$645 + 75 +
110 = $830.
|
|